Circular July 2008

3 x 1.1 MW Caterpillar
Gen.Sets
already in container
type g 3516b model natural gas
1165 kw / 50hz / 1500 rpm
with 11 sm g-36 merlin gerin
med. voltage cells (schneider electric)
with 3 ABB trafo step up 34.5 / 0.4 kv 1600 kva (oil type)
heat recovery system
boiler, heat exchange

CONTROL SYSTEM /
SYNCHRONIZATION UNIT
Working hours : 1-
15.070
2- 15.761
3- 17.511
W,TH 1 EACH Hilkar Neutral
Resistance 20 Ohms, 1000 Amp.
Price: 950,000.- Euro
For more information ask by Email
Several new unused Frame 9'S
Fuel: Set up for Liquid Fuel (DIESEL 2).
GE Frame 9 Gas Turbine Packaged Power Plants
PERFORMANCES: SIMPLE CYCLE
Output Power: 126 MW
Heat Rate: 10096 BTU/KWh (10650 kJ/kWh) (natural gas)
Model Structure
Type Standard Standard Standard
Fuel Natural Gas Distillate Oil Heavy Oil
Output 126100 kW 123300 kW 115300 kW
Heat Rate(LHV) 10650 kJ/kWh 10730 kJ/kWh 10960 kJ/kWh
Heat Cons(LHV) 1343×106 kJ/h 1328×106 kJ/h1263.7×106 kJ/h
Exhaust Temp 543 543 520
Exhaust Flow 1505×103kg/h 1509×103kg/h 1508.6×103kg/h
Shaft Speed 3000r/min 3000r/min 3000r/min
1-year of manufactured: 2007
2-location: Europe
3-how many hours working NONE - these are NEW - unused.
4-guarantee At this stage, warranty will only provided under an O&M contract.
SCOPE, LIMITS AND EXCLUSION FROM THE SUPPLY
Scope of Supply
1. Gas turbine generator package
2. Mechanical
• Gas Turbine
• Air Compressor
• Combustors
• Turning and Reduction Gear
• Air Inlet facilities (Filters and Ducts)
• Exhaust facilities (Ducts, Silencer) (less exhaust elbow )
• Starting Motor system
• Dual Fuel Combustors
• Lube and Control Oil System
• Closed Circuit Cooling Water system
• Atomizing and Cleaning system
• Instrument Air system
• Enclosures, including HVAC,
Fire-fighting, Electrical Switchboard for:
- Gas turbine unit (external and internal)
- Gas turbine auxiliaries
- Electrical Switchgear
- Control
- Closed Circuit auxiliaries
- Water Injection
• GT Supervision, Control and Protection Systems
• Fire Fighting (detection and protection) system
• Gas Detection system
• Thermal Insulation and Lagging
• Compressor Washing and Cleaning facilities
3. Electrical
• Electrical Generator, auxiliaries and related equipment (Circuit Breaker,
Grounding Switch, Bus duct, Neutral Grounding cubicle, etc.)
• Starting Motor system
• Unit Transformer (11/6 kV) and auxiliary MV/LV Transformers
• Main Switchboards (6 kV, 380 V PC, 380 MCC and emergency MCC) and MV
isolated bus ducts
• Auxiliary Switchboards (Generator Protection, HVAC, Fire-fighting, Lifting
facilities, etc)
• 110 DC Power System
• Uninterruptible Power System (UPS)
• AC/DC Electrical Motors (DC Motor starters included)
• Electrical Protection system
• Lighting and Motive Power system, Heat tracing, Grounding, etc.
• Cables and Cable Trays
4. Instrumentation & Controls
• On board Instrumentation
• Instrument Panels and Junction boxes
• Control, Protection and Monitoring Panels
• MMI (man-machine interface)
5. Miscellaneous
• Special Tools
• Anchor Bolts and Plates
• Stair and Ladders
• Steel Structures
6. Special Tools and Maintenance equipment (for the above mentioned machinery)
7. Operating and Maintenance Manuals
PERFORMANCES: SIMPLE CYCLE
The following Gas Turbine performances:
ISO Conditions
With reference to the following conditions:
Ambient Pressure: 1013 mbar
Ambient Temperature: 15 °C
Relative Humidity: 60 %
Gas Turbine Inlet/Exhaust Pressure drop: 89/127 mm H2O
The Plant Performances at Generator terminals when the plant is operated at GT new and clean conditions shall be:
Base Load
Output Power: 126 MW
Heat Rate: 10096 BTU/KWh (10650 kJ/kWh) (natural gas)
Price: For more information ask by Email