 MITSUBISHI 144 MW – 701D GAS TURBINE SPECIFICATION

Standby emergency for a Nuclear power station Lifetime fired hours 5,429.77 with 620 starts Upgrade and modernization to Nuclear standard in 2009 900 hours since upgrade

(1) Gas Turbine

Type : Open Simple Cycle Single Shaft Speed: 3,000 rpm Capacity 144 Mw Design base Inlet Air Temp 5 C Atm Pressure: 1,033 kg/cm3 abs Relative Humidity: 60% Fuel : Light Oil or City Gas Light Oil Specific Gravity: 0.83 HHV:10,800 kcal/kg *City Gas Specific Gravity:0.847 (kg/m3N) HHV: 11,000kcal/kg NOx control Water Injection + High Temp. Nox Denitration NOx Limited Value G/T Outlet: not more than 50ppm (at 02-16%) Denitration Outlet : not more than 20ppm (at 02-16%)

(2) Generator Type:

Cylindrical Rotating Field Type Three Phase Synchronous Generator Rating Item: Apparent Output Power Factor Relative Output Terminal Voltage Frequency No.of Pole, Speed Cooling Method Insulation 160,000 KVA (at 5oC) 90% 144,000 kw 15,000 V 50 Hz 2 pole, 3,000 rpm Open Air Cooling Class F Excitor Brushless Type using Silicon Rectifier and excitor Coupled with the Generator Textfeld: Out of scope 	
	(1) 	Main transformer. 
	(2) 	SCR. 
	(3) 	Power and control cable. 
	(4) 	Pipe work between equipment and other equipment. 
	(5) 	Foundation bolts and plates. 
	(6) 	Out door lighting system. 

Price: 24.6 Million USD 
Removal shared cost, seller/buyer 375k USD to dock.